Sign In | Join Free | My infospaceinc.com
China Wuhan Hertz Power Equipment Co., Ltd logo
Wuhan Hertz Power Equipment Co., Ltd
Deliver value to customers, contribute value to society, and thus fulfill personal value.
Verified Supplier

1 Years

Home > Power Transformer Testing Equipment >

HZYZ-2008 Transformer On-load Switch Tester

Wuhan Hertz Power Equipment Co., Ltd
Trust Seal
Verified Supplier
Credit Check
Supplier Assessment
Contact Now

HZYZ-2008 Transformer On-load Switch Tester

MOQ : 1

Test Range : 1-40Ω

Delivery Time : 5-7 working days

value : 7 kilograms

Brand Name : HZRTZ POWER

Gas Content : <=0.1~0.3%

Price : USD 1,000 - 10,000

Place of Origin : Wuhan, Hubei Province

Packaging Details : IPPC Fumigated wooden box (lSPM15)

Usage : On-load Tap-changer Characteristics Test

Model Number : HZYZ-2008

parameter : Weight

Certification : GB/T19001-2016 idt ISO 9001:2015

Test Voltage Accuracy : 1%

Resolution : 0.1μΩ

Payment Terms : T/T

Capacity Range : 10~100000KVA distribution transformer

Contact Now

Product Overview

The on-load tap changer is the only moving part connected to the transformer circuit. The HZYZ-2008 On-Load Tap Changer Tester is specifically engineered to measure the transition waveform, transition time, transition resistance values at each moment, and three-phase simultaneity of on-load tap changers in transformers.

Key Features
  • Resists high heat, humidity, and salt spray for tropical island use
  • Runs stably at -40°C, cold-proof and anti-condensation
  • IEC compliant, with complete calibration certificates provided
  • Local support available: spares, on-site training, and instrument calibration

HZYZ-2008 Transformer On-load Switch Tester

Product Attributes
FOB Unit
Set
MOQ
1
Packaging & Delivery
Not specified
Technical Specifications
Parameter Value
Output current 1.0A, 0.5A, and 0.2A
Measurement range (Resistance) 0.3Ω to 20Ω (1.0A), 5Ω to 40Ω (0.5A), 20Ω to 100Ω (0.2A)
Transition time 0 to 320ms
Open-circuit voltage 24V
Accuracy (Resistance) ±(5% reading ±0.1Ω)
Accuracy (Time) ±(0.1% reading ±0.2ms)
Sampling rate 20kHz
Storage method Local storage
External dimensions 340mm × 245mm × 210mm
Weight 7 kilograms

Product Tags:

Transformer On load Switch Tester

      

24V power transformer testing equipment

      

Transformer Switch Tester

      
Quality HZYZ-2008 Transformer On-load Switch Tester for sale

HZYZ-2008 Transformer On-load Switch Tester Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Wuhan Hertz Power Equipment Co., Ltd
*Subject:
*Message:
Characters Remaining: (0/3000)