| Sign In | Join Free | My infospaceinc.com |
|
MOQ : 1
Test Range : 1-40Ω
Delivery Time : 5-7 working days
value : 7 kilograms
Brand Name : HZRTZ POWER
Gas Content : <=0.1~0.3%
Price : USD 1,000 - 10,000
Place of Origin : Wuhan, Hubei Province
Packaging Details : IPPC Fumigated wooden box (lSPM15)
Usage : On-load Tap-changer Characteristics Test
Model Number : HZYZ-2008
parameter : Weight
Certification : GB/T19001-2016 idt ISO 9001:2015
Test Voltage Accuracy : 1%
Resolution : 0.1μΩ
Payment Terms : T/T
Capacity Range : 10~100000KVA distribution transformer
The on-load tap changer is the only moving part connected to the transformer circuit. The HZYZ-2008 On-Load Tap Changer Tester is specifically engineered to measure the transition waveform, transition time, transition resistance values at each moment, and three-phase simultaneity of on-load tap changers in transformers.

| Parameter | Value |
|---|---|
| Output current | 1.0A, 0.5A, and 0.2A |
| Measurement range (Resistance) | 0.3Ω to 20Ω (1.0A), 5Ω to 40Ω (0.5A), 20Ω to 100Ω (0.2A) |
| Transition time | 0 to 320ms |
| Open-circuit voltage | 24V |
| Accuracy (Resistance) | ±(5% reading ±0.1Ω) |
| Accuracy (Time) | ±(0.1% reading ±0.2ms) |
| Sampling rate | 20kHz |
| Storage method | Local storage |
| External dimensions | 340mm × 245mm × 210mm |
| Weight | 7 kilograms |
|
|
HZYZ-2008 Transformer On-load Switch Tester Images |